APC Transfer Limits for Input Voltage

Posted by paris on Oct 9, 2017 in Research

Per the user guide

http://www.apc.com/salestools/PMAR-8P9G2C/PMAR-8P9G2C_R2_EN.pdf

The below commands help you change the alerts on a UPS Network Management Card 2 using SSH , cannot be done via Web Interface 

cfgpower -all ( Show all applicable power parameters for this UPS. ) 

cfgpower -l ( 97–106 Set the low transfer point, in VAC. ) 

cfgpower -h (127–136 Set the high transfer point, in VAC.)

cfgpowerov (100 | 120 | 110 |) – Set the outlet voltage, in VAC.

cfgpower -s Normal | Reduced | Low ) – Set the sensitivity, using one of the three arguments.

cfgpower -bu (127 | 130 | 133 |136 | 139 | 142 |145 | 148 ) – Set the bypass upper voltage in VAC; when the voltage rises above this value, the device goes into bypass. )

cfgpower -bl (086 | 088 | 090 | 092 | 094 | 096 | 098 | 100 ) – Set the bypass lower voltage in VAC; when the voltage drops below this value, the device goes into bypass. )

VN:F [1.9.22_1171]
Rating: 0.0/10 (0 votes cast)
VN:F [1.9.22_1171]
Rating: 0 (from 0 votes)

Tags: , , , , , , , , , , , , , , ,

 
0

Find VM’s using e1000 Adapter Running Windows

Posted by paris on Feb 16, 2017 in Random

Powershell script to list machines running  the out of date e1000 Adapter in Windows so you can update them to VMXnet3 !

Get-VM |
 
Where{(Get-NetworkAdapter -VM $_ | where{$_.Type -eq 'e1000'}) -and (Get-VMguest -VM $_ | Where-Object {$_.OSFullName -like "*Windows Server*"})} |
 
Select Name,@{N='vCenter';E={$_.Uid.Split('@')[1].Split(':')[0]}}

 

 

VN:F [1.9.22_1171]
Rating: 0.0/10 (0 votes cast)
VN:F [1.9.22_1171]
Rating: 0 (from 0 votes)

Tags: , , , , , , ,

Copyright © 2017 Welcome to Pariswells.com All rights reserved. Theme by Laptop Geek. Privacy Policy