{"id":2838,"date":"2017-10-09T05:03:12","date_gmt":"2017-10-09T05:03:12","guid":{"rendered":"http:\/\/pariswells.com\/blog\/?p=2838"},"modified":"2017-10-09T05:03:12","modified_gmt":"2017-10-09T05:03:12","slug":"apc-transfer-limits-for-input-voltage","status":"publish","type":"post","link":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage","title":{"rendered":"APC Transfer Limits for Input Voltage"},"content":{"rendered":"<p>Per the user guide<\/p><p><a href=\"http:\/\/www.apc.com\/salestools\/PMAR-8P9G2C\/PMAR-8P9G2C_R2_EN.pdf\">http:\/\/www.apc.com\/salestools\/PMAR-8P9G2C\/PMAR-8P9G2C_R2_EN.pdf<\/a><\/p><p>The below commands help you change the alerts on a\u00a0UPS Network Management Card 2 using SSH , cannot be done via Web Interface\u00a0<\/p><p style=\"padding-left: 30px;\">cfgpower<strong>\u00a0-all<\/strong> (\u00a0Show all applicable power parameters for this UPS. )\u00a0<\/p><p style=\"padding-left: 30px;\">cfgpower<strong>\u00a0-l<\/strong> (\u00a097\u2013106 Set the low transfer point, in VAC. )\u00a0<\/p><p style=\"padding-left: 30px;\">cfgpower<strong> -h<\/strong> (127\u2013136 Set the high transfer point, in VAC.)<br \/><br \/>cfgpower<strong> &#8211;<\/strong>ov<strong>\u00a0(100 | 120 | 110 |)<\/strong> &#8211; Set the outlet voltage, in VAC.<br \/><br \/>cfgpower<strong> -s Normal | Reduced | Low )<\/strong> &#8211; Set the sensitivity, using one of the three arguments.<br \/><br \/>cfgpower<strong> -bu (127 | 130 | 133 |136 | 139 | 142 |145 | 148 )<\/strong> &#8211; Set the bypass upper voltage in VAC; when the voltage rises above this value, the device goes into bypass. )<br \/><br \/>cfgpower<strong> -bl (086 | 088 | 090 | 092 | 094 | 096 |\u00a0098 | 100 )<\/strong>\u00a0&#8211; Set the bypass lower voltage in VAC; when the voltage drops below this value, the device goes into bypass. )<\/p>","protected":false},"excerpt":{"rendered":"<p>Per the user guidehttp:\/\/www.apc.com\/salestools\/PMAR-8P9G2C\/PMAR-8P9G2C_R2_EN.pdfThe below commands help you change the alerts on a\u00a0UPS Network Management Card 2 using SSH , cannot be done via Web Interface\u00a0cfgpower\u00a0-all (\u00a0Show [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[1],"tags":[2142,2144,2145,2141,1751,2150,2148,2149,2151,2152,2143,1511,2154,2153,2146,2147],"class_list":["post-2838","post","type-post","status-publish","format-standard","hentry","category-research","tag-apc","tag-bypass-lower","tag-bypass-upper","tag-cfgpower","tag-cli","tag-compensating","tag-compensating-for-a-high-input-voltage","tag-compensating-for-a-low-input-voltage","tag-high-input-voltage","tag-low-input-voltage","tag-transfer-point","tag-ups","tag-ups-network-management-card","tag-ups-network-management-card-2","tag-vac","tag-voltage"],"aioseo_notices":[],"aioseo_head":"\n\t\t<!-- All in One SEO 4.9.8 - aioseo.com -->\n\t<meta name=\"description\" content=\"Per the user guidehttp:\/\/www.apc.com\/salestools\/PMAR-8P9G2C\/PMAR-8P9G2C_R2_EN.pdfThe below commands help you change the alerts on a UPS Network Management Card 2 using SSH , cannot be done via Web Interface cfgpower -all ( Show all applicable power parameters for this UPS. ) cfgpower -l ( 97\u2013106 Set the low transfer point, in VAC. ) cfgpower -h (127\u2013136 Set the high transfer point, in VAC.)cfgpower -ov (100 |\" \/>\n\t<meta name=\"robots\" content=\"max-image-preview:large\" \/>\n\t<meta name=\"author\" content=\"paris\"\/>\n\t<link rel=\"canonical\" href=\"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage\" \/>\n\t<meta name=\"generator\" content=\"All in One SEO (AIOSEO) 4.9.8\" \/>\n\t\t<meta property=\"og:locale\" content=\"en_US\" \/>\n\t\t<meta property=\"og:site_name\" content=\"Welcome to Pariswells.com |\" \/>\n\t\t<meta property=\"og:type\" content=\"article\" \/>\n\t\t<meta property=\"og:title\" content=\"APC Transfer Limits for Input Voltage | Welcome to Pariswells.com\" \/>\n\t\t<meta property=\"og:description\" content=\"Per the user guidehttp:\/\/www.apc.com\/salestools\/PMAR-8P9G2C\/PMAR-8P9G2C_R2_EN.pdfThe below commands help you change the alerts on a UPS Network Management Card 2 using SSH , cannot be done via Web Interface cfgpower -all ( Show all applicable power parameters for this UPS. ) cfgpower -l ( 97\u2013106 Set the low transfer point, in VAC. ) cfgpower -h (127\u2013136 Set the high transfer point, in VAC.)cfgpower -ov (100 |\" \/>\n\t\t<meta property=\"og:url\" content=\"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage\" \/>\n\t\t<meta property=\"article:published_time\" content=\"2017-10-09T05:03:12+00:00\" \/>\n\t\t<meta property=\"article:modified_time\" content=\"2017-10-09T05:03:12+00:00\" \/>\n\t\t<meta name=\"twitter:card\" content=\"summary\" \/>\n\t\t<meta name=\"twitter:title\" content=\"APC Transfer Limits for Input Voltage | Welcome to Pariswells.com\" \/>\n\t\t<meta name=\"twitter:description\" content=\"Per the user guidehttp:\/\/www.apc.com\/salestools\/PMAR-8P9G2C\/PMAR-8P9G2C_R2_EN.pdfThe below commands help you change the alerts on a UPS Network Management Card 2 using SSH , cannot be done via Web Interface cfgpower -all ( Show all applicable power parameters for this UPS. ) cfgpower -l ( 97\u2013106 Set the low transfer point, in VAC. ) cfgpower -h (127\u2013136 Set the high transfer point, in VAC.)cfgpower -ov (100 |\" \/>\n\t\t<script type=\"application\/ld+json\" class=\"aioseo-schema\">\n\t\t\t{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/research\\\/apc-transfer-limits-for-input-voltage#article\",\"name\":\"APC Transfer Limits for Input Voltage | Welcome to Pariswells.com\",\"headline\":\"APC Transfer Limits for Input Voltage\",\"author\":{\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/author\\\/paris#author\"},\"publisher\":{\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/#organization\"},\"datePublished\":\"2017-10-09T05:03:12+00:00\",\"dateModified\":\"2017-10-09T05:03:12+00:00\",\"inLanguage\":\"en-US\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/research\\\/apc-transfer-limits-for-input-voltage#webpage\"},\"isPartOf\":{\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/research\\\/apc-transfer-limits-for-input-voltage#webpage\"},\"articleSection\":\"Research, apc, bypass lower, bypass upper, cfgpower, cli, Compensating, Compensating for a high input voltage, Compensating for a Low input voltage, high input voltage, low input voltage, transfer point, UPS, UPS Network Management Card, UPS Network Management Card 2, VAC, voltage\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/research\\\/apc-transfer-limits-for-input-voltage#breadcrumblist\",\"itemListElement\":[{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog#listItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/pariswells.com\\\/blog\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/category\\\/research#listItem\",\"name\":\"Research\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/category\\\/research#listItem\",\"position\":2,\"name\":\"Research\",\"item\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/category\\\/research\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/research\\\/apc-transfer-limits-for-input-voltage#listItem\",\"name\":\"APC Transfer Limits for Input Voltage\"},\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog#listItem\",\"name\":\"Home\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/research\\\/apc-transfer-limits-for-input-voltage#listItem\",\"position\":3,\"name\":\"APC Transfer Limits for Input Voltage\",\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/category\\\/research#listItem\",\"name\":\"Research\"}}]},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/#organization\",\"name\":\"Welcome to Pariswells.com\",\"url\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/author\\\/paris#author\",\"url\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/author\\\/paris\",\"name\":\"paris\",\"image\":{\"@type\":\"ImageObject\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/research\\\/apc-transfer-limits-for-input-voltage#authorImage\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/93b8ee3f592ac401167f870452bd82d43de80152cd3524e2853403658ada9984?s=96&d=mm&r=g\",\"width\":96,\"height\":96,\"caption\":\"paris\"}},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/research\\\/apc-transfer-limits-for-input-voltage#webpage\",\"url\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/research\\\/apc-transfer-limits-for-input-voltage\",\"name\":\"APC Transfer Limits for Input Voltage | Welcome to Pariswells.com\",\"description\":\"Per the user guidehttp:\\\/\\\/www.apc.com\\\/salestools\\\/PMAR-8P9G2C\\\/PMAR-8P9G2C_R2_EN.pdfThe below commands help you change the alerts on a UPS Network Management Card 2 using SSH , cannot be done via Web Interface cfgpower -all ( Show all applicable power parameters for this UPS. ) cfgpower -l ( 97\\u2013106 Set the low transfer point, in VAC. ) cfgpower -h (127\\u2013136 Set the high transfer point, in VAC.)cfgpower -ov (100 |\",\"inLanguage\":\"en-US\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/#website\"},\"breadcrumb\":{\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/research\\\/apc-transfer-limits-for-input-voltage#breadcrumblist\"},\"author\":{\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/author\\\/paris#author\"},\"creator\":{\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/author\\\/paris#author\"},\"datePublished\":\"2017-10-09T05:03:12+00:00\",\"dateModified\":\"2017-10-09T05:03:12+00:00\"},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/#website\",\"url\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/\",\"name\":\"Welcome to Pariswells.com\",\"inLanguage\":\"en-US\",\"publisher\":{\"@id\":\"https:\\\/\\\/pariswells.com\\\/blog\\\/#organization\"}}]}\n\t\t<\/script>\n\t\t<!-- All in One SEO -->\n\n","aioseo_head_json":{"title":"APC Transfer Limits for Input Voltage | Welcome to Pariswells.com","description":"Per the user guidehttp:\/\/www.apc.com\/salestools\/PMAR-8P9G2C\/PMAR-8P9G2C_R2_EN.pdfThe below commands help you change the alerts on a UPS Network Management Card 2 using SSH , cannot be done via Web Interface cfgpower -all ( Show all applicable power parameters for this UPS. ) cfgpower -l ( 97\u2013106 Set the low transfer point, in VAC. ) cfgpower -h (127\u2013136 Set the high transfer point, in VAC.)cfgpower -ov (100 |","canonical_url":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage","robots":"max-image-preview:large","keywords":"","webmasterTools":{"miscellaneous":""},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage#article","name":"APC Transfer Limits for Input Voltage | Welcome to Pariswells.com","headline":"APC Transfer Limits for Input Voltage","author":{"@id":"https:\/\/pariswells.com\/blog\/author\/paris#author"},"publisher":{"@id":"https:\/\/pariswells.com\/blog\/#organization"},"datePublished":"2017-10-09T05:03:12+00:00","dateModified":"2017-10-09T05:03:12+00:00","inLanguage":"en-US","mainEntityOfPage":{"@id":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage#webpage"},"isPartOf":{"@id":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage#webpage"},"articleSection":"Research, apc, bypass lower, bypass upper, cfgpower, cli, Compensating, Compensating for a high input voltage, Compensating for a Low input voltage, high input voltage, low input voltage, transfer point, UPS, UPS Network Management Card, UPS Network Management Card 2, VAC, voltage"},{"@type":"BreadcrumbList","@id":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage#breadcrumblist","itemListElement":[{"@type":"ListItem","@id":"https:\/\/pariswells.com\/blog#listItem","position":1,"name":"Home","item":"https:\/\/pariswells.com\/blog","nextItem":{"@type":"ListItem","@id":"https:\/\/pariswells.com\/blog\/category\/research#listItem","name":"Research"}},{"@type":"ListItem","@id":"https:\/\/pariswells.com\/blog\/category\/research#listItem","position":2,"name":"Research","item":"https:\/\/pariswells.com\/blog\/category\/research","nextItem":{"@type":"ListItem","@id":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage#listItem","name":"APC Transfer Limits for Input Voltage"},"previousItem":{"@type":"ListItem","@id":"https:\/\/pariswells.com\/blog#listItem","name":"Home"}},{"@type":"ListItem","@id":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage#listItem","position":3,"name":"APC Transfer Limits for Input Voltage","previousItem":{"@type":"ListItem","@id":"https:\/\/pariswells.com\/blog\/category\/research#listItem","name":"Research"}}]},{"@type":"Organization","@id":"https:\/\/pariswells.com\/blog\/#organization","name":"Welcome to Pariswells.com","url":"https:\/\/pariswells.com\/blog\/"},{"@type":"Person","@id":"https:\/\/pariswells.com\/blog\/author\/paris#author","url":"https:\/\/pariswells.com\/blog\/author\/paris","name":"paris","image":{"@type":"ImageObject","@id":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage#authorImage","url":"https:\/\/secure.gravatar.com\/avatar\/93b8ee3f592ac401167f870452bd82d43de80152cd3524e2853403658ada9984?s=96&d=mm&r=g","width":96,"height":96,"caption":"paris"}},{"@type":"WebPage","@id":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage#webpage","url":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage","name":"APC Transfer Limits for Input Voltage | Welcome to Pariswells.com","description":"Per the user guidehttp:\/\/www.apc.com\/salestools\/PMAR-8P9G2C\/PMAR-8P9G2C_R2_EN.pdfThe below commands help you change the alerts on a UPS Network Management Card 2 using SSH , cannot be done via Web Interface cfgpower -all ( Show all applicable power parameters for this UPS. ) cfgpower -l ( 97\u2013106 Set the low transfer point, in VAC. ) cfgpower -h (127\u2013136 Set the high transfer point, in VAC.)cfgpower -ov (100 |","inLanguage":"en-US","isPartOf":{"@id":"https:\/\/pariswells.com\/blog\/#website"},"breadcrumb":{"@id":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage#breadcrumblist"},"author":{"@id":"https:\/\/pariswells.com\/blog\/author\/paris#author"},"creator":{"@id":"https:\/\/pariswells.com\/blog\/author\/paris#author"},"datePublished":"2017-10-09T05:03:12+00:00","dateModified":"2017-10-09T05:03:12+00:00"},{"@type":"WebSite","@id":"https:\/\/pariswells.com\/blog\/#website","url":"https:\/\/pariswells.com\/blog\/","name":"Welcome to Pariswells.com","inLanguage":"en-US","publisher":{"@id":"https:\/\/pariswells.com\/blog\/#organization"}}]},"og:locale":"en_US","og:site_name":"Welcome to Pariswells.com |","og:type":"article","og:title":"APC Transfer Limits for Input Voltage | Welcome to Pariswells.com","og:description":"Per the user guidehttp:\/\/www.apc.com\/salestools\/PMAR-8P9G2C\/PMAR-8P9G2C_R2_EN.pdfThe below commands help you change the alerts on a UPS Network Management Card 2 using SSH , cannot be done via Web Interface cfgpower -all ( Show all applicable power parameters for this UPS. ) cfgpower -l ( 97\u2013106 Set the low transfer point, in VAC. ) cfgpower -h (127\u2013136 Set the high transfer point, in VAC.)cfgpower -ov (100 |","og:url":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage","article:published_time":"2017-10-09T05:03:12+00:00","article:modified_time":"2017-10-09T05:03:12+00:00","twitter:card":"summary","twitter:title":"APC Transfer Limits for Input Voltage | Welcome to Pariswells.com","twitter:description":"Per the user guidehttp:\/\/www.apc.com\/salestools\/PMAR-8P9G2C\/PMAR-8P9G2C_R2_EN.pdfThe below commands help you change the alerts on a UPS Network Management Card 2 using SSH , cannot be done via Web Interface cfgpower -all ( Show all applicable power parameters for this UPS. ) cfgpower -l ( 97\u2013106 Set the low transfer point, in VAC. ) cfgpower -h (127\u2013136 Set the high transfer point, in VAC.)cfgpower -ov (100 |"},"aioseo_meta_data":{"post_id":"2838","title":null,"description":null,"keywords":null,"keyphrases":null,"canonical_url":null,"og_title":null,"og_description":null,"og_object_type":"default","og_image_type":"default","og_image_url":null,"og_image_width":null,"og_image_height":null,"og_image_custom_url":null,"og_image_custom_fields":null,"og_video":null,"og_custom_url":null,"og_article_section":null,"og_article_tags":null,"twitter_use_og":false,"twitter_card":"default","twitter_image_type":"default","twitter_image_url":null,"twitter_image_custom_url":null,"twitter_image_custom_fields":null,"twitter_title":null,"twitter_description":null,"schema":{"blockGraphs":[],"customGraphs":[],"default":{"data":{"Article":[],"Course":[],"Dataset":[],"FAQPage":[],"Movie":[],"Person":[],"Product":[],"ProductReview":[],"Car":[],"Recipe":[],"Service":[],"SoftwareApplication":[],"WebPage":[]},"graphName":"","isEnabled":true},"graphs":[]},"schema_type":null,"schema_type_options":null,"pillar_content":false,"robots_default":true,"robots_noindex":false,"robots_noarchive":false,"robots_nosnippet":false,"robots_nofollow":false,"robots_noimageindex":false,"robots_noodp":false,"robots_notranslate":false,"robots_max_snippet":null,"robots_max_videopreview":null,"robots_max_imagepreview":"large","priority":null,"frequency":null,"location":null,"local_seo":null,"breadcrumb_settings":null,"limit_modified_date":false,"ai":null,"created":"2020-12-21 05:39:33","updated":"2022-09-17 01:41:08","primary_term":null,"seo_analyzer_scan_date":null},"aioseo_breadcrumb":"<div class=\"aioseo-breadcrumbs\"><span class=\"aioseo-breadcrumb\">\n\t\t\t<a href=\"https:\/\/pariswells.com\/blog\" title=\"Home\">Home<\/a>\n\t\t<\/span><span class=\"aioseo-breadcrumb-separator\">&raquo;<\/span><span class=\"aioseo-breadcrumb\">\n\t\t\t<a href=\"https:\/\/pariswells.com\/blog\/category\/research\" title=\"Research\">Research<\/a>\n\t\t<\/span><span class=\"aioseo-breadcrumb-separator\">&raquo;<\/span><span class=\"aioseo-breadcrumb\">\n\t\t\tAPC Transfer Limits for Input Voltage\n\t\t<\/span><\/div>","aioseo_breadcrumb_json":[{"label":"Home","link":"https:\/\/pariswells.com\/blog"},{"label":"Research","link":"https:\/\/pariswells.com\/blog\/category\/research"},{"label":"APC Transfer Limits for Input Voltage","link":"https:\/\/pariswells.com\/blog\/research\/apc-transfer-limits-for-input-voltage"}],"_links":{"self":[{"href":"https:\/\/pariswells.com\/blog\/wp-json\/wp\/v2\/posts\/2838","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/pariswells.com\/blog\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/pariswells.com\/blog\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/pariswells.com\/blog\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/pariswells.com\/blog\/wp-json\/wp\/v2\/comments?post=2838"}],"version-history":[{"count":3,"href":"https:\/\/pariswells.com\/blog\/wp-json\/wp\/v2\/posts\/2838\/revisions"}],"predecessor-version":[{"id":2882,"href":"https:\/\/pariswells.com\/blog\/wp-json\/wp\/v2\/posts\/2838\/revisions\/2882"}],"wp:attachment":[{"href":"https:\/\/pariswells.com\/blog\/wp-json\/wp\/v2\/media?parent=2838"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/pariswells.com\/blog\/wp-json\/wp\/v2\/categories?post=2838"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/pariswells.com\/blog\/wp-json\/wp\/v2\/tags?post=2838"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}